Compressed Air Flow Meter – 40-600 SCFM Sensor T-CDI-5400-20S

Effectively monitor compressed air systems with the T-CDI-5400-20S. This flow meter includes two probes, one warmer than the other. This arrangement calculates mass velocity based on heat requirements. Additionally, pipe area data is used to determine flow amounts. This product fits a two-inch steel pipe.

Requires analog port selection during U30 system configuration and use of a S-FS-CVIA when using the H22-001 data logger. When using a U12 data logger, this sensor requires a 4-20mA input cable (CABLE-4-20mA).

Deskripsi

Highlighted Features

  • This adds the ability for users to be able to measure compressed air flow (SCFM).
  • Easy to install
  • Digital display

In what environment does this sensor operate?

This sensor operates in an indoor environment.

What measurements does this sensor support?

The T-CDI-5400-20S sensor supports the following measurement: Compressed Air Flow

To see the full specifications for this product, please see our product manual found under the documentation tab if available

Measurement range: 40-600 SCFM (calibrated), 350 – 600 (uncalibrated)
Accuracy: 5% of reading plus 1% of full scale @ air temperatures 40 – 120F; (5400 model extended range) 7% of reading from rated fule scale to 150% of calibrated range, @ air temperatures 40 – 120F
Medium: Compressed air, nitrogen
Operating pressure: 200 psig max on Sch 40 steel
Input power: 250 mA @ 18 – 24 VDC
Output resistance: 400Ω max
Response time: 1 sec to 63% of final value
Output: selectable 4 – 20mA or pulse
Display: 4-digit LED
Ring material: Aluminum
Size / Weight: 3.2×2.2×1.6 in / approx. 1.4 lb

Note: Recommended: Drill Guide that facilitates accurately locating the holes that are needed to mount the flowmeter.

Ulasan

Belum ada ulasan.

Jadilah yang pertama memberikan ulasan “Compressed Air Flow Meter – 40-600 SCFM Sensor T-CDI-5400-20S”

Alamat email Anda tidak akan dipublikasikan. Ruas yang wajib ditandai *